In the construction of 5G network infrastructure, the cooling performance of outdoor communication cabinets directly impacts equipment stability and service life. According to the latest data from the Ministry of Industry and Information Technology, the total number of 5G base stations in China exceeded 2.8 million in 2023, with approximately 65% deployed in outdoor cabinets. These cabinets face the following challenges:
- Continuously increasing power density of equipment (average power consumption 2.5 times higher than 4G)
- Year-round uninterrupted operation requirements (availability target of 99.999%)
- Complex environmental challenges (operating temperature range: -40℃ to +70℃)
- Strict energy efficiency standards (PUE requirement <1.5)
Limitations Due to Protection Features
- Sealed structures hinder natural convection cooling
- Dust filters increase airflow resistance (pressure drop typically 30-50Pa)
- Waterproof requirements restrict opening ratios and locations
Cooling System Must Meet the Following Requirements
1. Sufficient air exchange rate (typically 20-40 times per hour)
2. Overcome additional airflow resistance from protective structures
3. Reliable operation across a wide temperature range
4. Maintain low noise levels (<55dB at 1m)
Technical Parameters of Centrifugal Fan
Parameter Category |
Technical Specifications |
Model |
PB3N310B48-ZZ7 |
Type |
Centrifugal Fan |
Dimensions |
310×310×148mm |
Rated Voltage |
48VDC |
Rated Current |
3.2A |
Rated Power |
150W |
Maximum Airflow |
680m³/h |
Maximum Static Pressure |
450Pa |
Noise Level |
52dB(A) at 1m |
Protection Level |
IP55 |
Bearing Type |
Double Ball Bearings |
Operating Temperature Range |
-30℃ to +70℃ |
Service Life |
70,000 hours (at 25℃ ambient temperature) |
- Uses backward-inclined aluminum alloy impeller optimized via CFD
- Blade count and angle specifically designed for airflow resistance in communication cabinets
- 18% higher efficiency compared to conventional products
- Supports dual-mode 0-10V/PWM speed regulation
- Built-in customizable temperature-speed curve
- Minimum adjustable speed: 30% (to maintain bearing lubrication)
- Shaft seal features labyrinth-style sealing with special materials
- Junction box complies with IP55 protection requirements
- All fasteners made of stainless steel
- Rotor dynamic balance grade: G2.5
- Motor windings use Class H insulation
- Bearings pre-lubricated with long-lasting grease
Suitable for small to medium-sized 5G communication cabinets (15-25U):
- Installation Position: Top of the cabinet (hot air naturally rises)
- Airflow Organization: Bottom-in, top-out vertical airflow
- Accessories:
- PBM dedicated dust filter (pressure drop <35Pa)
- Airflow guide cover (reduces vortex loss)
- Vibration-damping pads (reduces structural noise transmission)
Suitable for large cabinets (30-42U) at critical nodes:
- Configuration:
- Primary fan: Operates at 100% speed
- Backup fan: Standby mode (30% speed)
- Switching Logic:
- Automatic switch when temperature >55℃ or primary fan failure
- Supports manual override
Test Condition |
Value |
Ambient Temperature |
38℃ (summer peak) |
Cabinet Heat Load |
1200W |
Operating Mode |
Automatic speed regulation |
Average Speed |
75% |
Internal Temperature Rise |
+14℃ (maximum大52℃) |
Daily Power Consumption |
2.4kWh |
Noise Level |
48dB(A)@1m |
1. Energy Efficiency: 23% lower power consumption than conventional fans
2. Temperature Control: Hotspot temperature difference <5℃ (traditional solutions >8℃)
3. Reliability: Zero failures over 18 months of continuous operation
4. Maintenance Costs: Filter replacement cycle extended to 9 months
Installation and Maintenance Guide
- Ensure arrow markings align with airflow direction
- Maintain ≥150mm clearance between air intake and obstacles
- Use cables with cross-sectional area ≥1.5mm²
- Apply waterproof treatment to terminal connections
- Conduct a 30-minute test run upon initial operation
- Verify smooth switching between speed settings
Maintenance Item |
Frequency |
Inspection Points |
Filter Cleaning |
3 months |
Replace if pressure drop >50Pa |
Fan Bearing Inspection |
12 months |
Check for abnormal noise and vibration |
Electrical Connection Check |
6 months |
Inspect terminal oxidation |
Impeller Dust Removal |
12 months |
Use compressed air for cleaning |
Technological Evolution and Customization Services
Pingyun Electric offers the following for special requirements:
- Coastal areas: Anti-corrosion coating (1000h salt spray test)
- Cold regions: Bearing heating devices (startup at -40℃)
- Add RS485 communication interface
- Support IoT platform integration
- Voltage adaptation (24V/380V, etc.)
- Explosion-proof version (Ex dⅡC T4)
The Pingyun Electric PB3N310B48-ZZ7 centrifugal fan, with its outstanding performance parameters and professional protection design, serves as an ideal cooling solution for IP55-rated 5G communication cabinets. By precisely matching cabinet heat loads, optimizing airflow organization, and implementing intelligent speed control, this solution ensures equipment reliability while significantly improving energy efficiency. As 5G networks evolve toward higher density and power, this engineering-validated professional cooling solution will demonstrate even greater value in practical applications.