280mm EC Single Inlet Blower is made especially for chemical waste gas treatment systems and laboratory fume hoods. It has an IP44 protection rating, a 380V EC motor with 1150 rpm speed, 3000 m³/h air volume, 650 Pa static pressure, 950 W of power, and a noise level of 79 dB (A). Airflow is effectively collected and pressurized by the single-inlet volute construction. In order to ensure a stable air velocity above 0.5 m/s at the fume hood surface and successfully remove hazardous gases produced during experiments, the 650 Pa static pressure is adequate to overcome the resistance of activated carbon filters, HEPA filters, and long-distance ductwork (including multiple bends). Two to three conventional fume hoods can be used simultaneously with the 3000 m³/h air volume. When paired with a VAV variable air volume system for dynamic adjustment, the EC motor's 0–10V/PWM speed control allows for substantial energy savings. It is appropriate for independent exhaust fan rooms with a noise level of 79 dB (A). It is the perfect power source for laboratory exhaust systems because of its IP44 rating, which can tolerate small chemical splashes, and its 50,000-hour lifespan, which guarantees long-term dependable operation for research institutes and inspection and quarantine facilities.
General Characters
|
1-1 |
Rated Voltage |
380 VAC |
|
1-2 |
Frequency |
50/60 Hz |
|
1-3 |
Operating Voltage |
304–456 VAC |
|
1-4 |
Rated Speed | 1150 RPM |
|
1-5 |
Input Current |
1.6 A |
|
1-6 |
Input Power |
950 W |
|
1-7 |
Air Flow |
1213 CFM / 3000 M³/H |
|
1-8 |
Static Pressure |
4.12 inH₂O / 650 Pa |
|
1-9 |
Acoustical Noise |
79 dB(A) |
|
1-10 |
Life Expectancy |
50,000 Hours (L10) At 40℃ room, humidity 15%~65%RH. |
|
1-11 |
Insulation Class |
Class F |
|
1-13 |
Motor Protection |
Locked rotor protection Polarity protection Automatic restart capability |
|
1-14 |
Speed Control |
Control input 0~10VDC / PWM |
|
1-15 |
Protection Type |
IP44 |
|
1-17 |
Signal Output |
FG (Frequency Generator) |
Mechanical Characters
|
2-1 |
Dimension |
485 mm X 528 mm X 242 mm (see dimension drawing) |
|
2-2 |
Material of Impeller |
Galvanized metal shell |
|
2-3 |
Number of Blades |
38 |
|
2-4 |
Bearing System |
NMB ball bearing |
|
2-5 |
Lead Wire |
AC (AWG18 #), DC (AWG22 #) |
Environmental Characters
|
3-1 |
Operating Temperature |
-25℃ to 60℃ |
|
3-2 |
Storage Temperature |
-40℃ to 75℃ |
|
3-3 |
Operating Humidity |
5% to 90% RH |
|
3-4 |
Storage Humidity |
5% to 95% RH |
Performance Curve
Testing Condition:
Input Voltage----Operating voltage (380VAC/50Hz)
Temperature-----Room temperature
Humidity---------65%RH
Outline Drawing
Note:
1.Connection line: AC(3×AWG18#),DC(4×AWG22#)
2.AC: Brown=L1(R),Blue=L2(S),Black=L3(T),Green & Yellow=Protecting Earthing;
3.DC: Red=Voltage Output +10VDC, Yellow=0-10VDC/PWM, White=FG, Blue=GND;